John Deere powered generators from Genset Central!


70 - 100kW John Deere Powered Generators

Generators Standard Features

  • John Deere Diesel Engine
  • Cool flow Radiator with fan guards
  • Dry Type - Air cleaner and oil filter with internal bypass
  • Oil and radiator drain extension
  • Battery charging alternator
  • Main Line Circuit Breaker
  • Battery, battery rack and cables
  • Vibration Isolators between engine/alternator and base frame
  • Optional double wall UL 142 listed fuel tanks 24, 48 and 72 hour run time
  • Optional sub base single wall fuel tank 26-50 gallons
Digital Control Panel features:

The generator set is controlled by an auto start control panel.  The control panel is skid mounted in a NEMA 1 enclosure and equipped with: on/off key switch, start/stop push buttons, emergency stop button and display for the indication of: AC volts, AC amps, Frequency, Oil pressure and Water temperature
Safety Shutdowns for:

High coolant Temp, Low Oil Pressure

2 Year Limited Warranty Standby Applications

 Model Specifications>> J70U J70UM J75UC J80U J100UC J100U
Standby kW 70 70 75 80 100 100
Phase 3 1 3 3 3 3
Engine Model 4045T 4045T 4045T 4045T 4045 4045H
Fuel use gph/75% 3.8 3.8 4.3 4.2 5.7 5.0
Non-UL Fuel Tank Gal 47 47 47 47 50 50
Weight lbs - Open. 2425 2535 2535 2425 2723 2723
L(x)W(x)H 74x40x54 74x40x54 74x40x54 74x40x54 77x43x53 77x43x53